This study investigates the possibility to contain COVID-19 contagion in indoor environments via increasing ventilation rates obtained through high energy efficiency systems combining thermal recovery by heat exchanger and thermodynamic recovery by heat pump. The starting point of this assessment is a procedure to evaluate in naturally ventilated environments, the current infectious risk by using measurements of indoor/outdoor CO2 concentrations to calculate actual air changes per hour. The method was applied to some typical school environments in Italy. The results indicated very infectious situations with reproduction number Ro values up to exceed 13. But, the simulations assessed an extraordinary reduction of indoor viral concentration and consequently of the infection risk by a strong mechanical ventilation. High ventilation rates make facemasks effective even with use levels (from 50%) reasonable also for pupils. This way, R0 goes down the value one. As regards energy performance, the behavior of an autonomous high efficiency air handling unit (HEAHU), to be installed in an existing naturally ventilated classroom, was simulated in the monitored days. The results highlight the ability to achieve a reduction in energy consumption between 60% and 72%.

High energy efficiency ventilation to limit COVID-19 contagion in school environments

Schibuola, Luigi;Tambani, Chiara
2021-01-01

Abstract

This study investigates the possibility to contain COVID-19 contagion in indoor environments via increasing ventilation rates obtained through high energy efficiency systems combining thermal recovery by heat exchanger and thermodynamic recovery by heat pump. The starting point of this assessment is a procedure to evaluate in naturally ventilated environments, the current infectious risk by using measurements of indoor/outdoor CO2 concentrations to calculate actual air changes per hour. The method was applied to some typical school environments in Italy. The results indicated very infectious situations with reproduction number Ro values up to exceed 13. But, the simulations assessed an extraordinary reduction of indoor viral concentration and consequently of the infection risk by a strong mechanical ventilation. High ventilation rates make facemasks effective even with use levels (from 50%) reasonable also for pupils. This way, R0 goes down the value one. As regards energy performance, the behavior of an autonomous high efficiency air handling unit (HEAHU), to be installed in an existing naturally ventilated classroom, was simulated in the monitored days. The results highlight the ability to achieve a reduction in energy consumption between 60% and 72%.
File in questo prodotto:
File Dimensione Formato  
Covid_1 Energy & Buildings 2021.pdf

accesso aperto

Descrizione: Articolo principale
Tipologia: Versione Editoriale
Licenza: DRM non definito
Dimensione 4.13 MB
Formato Adobe PDF
4.13 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11578/299783
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 93
  • ???jsp.display-item.citation.isi??? 78
social impact