A promising district heating concept consists of distributing the heat at temperatures below 45 °C and using booster heat pumps at the customers' substations to provide the appropriate temperature needed for space heating and domestic hot water production. As such, thermal networks would be able to abate heat losses and substantially increase the number of recoverable heat sources. At the same time, the supply temperature from the booster heat pumps can be tailored to the building supplied instead of being based on the most critical consumer. This work investigates the performance of booster heat pumps assuming network supply temperatures in the range between 15 °C and 45 °C. The impact of supply and return temperature on the levelized cost of heat for different end users was assessed. The parametric study shows the importance of the nominal network temperature difference in the design phase of the system in order to reach a good trade-off between initial investment and operating costs. The economic analysis shows that the system is already competitive with individual gas boilers provided that a local low-temperature heat source can be recovered with minor marginal costs.

Evaluating the cost of heat for end users in ultra low temperature district heating networks with booster heat pumps

Vivian, Jacopo;Emmi, Giuseppe;Zarrella, Angelo;De Carli, Michele
2018-01-01

Abstract

A promising district heating concept consists of distributing the heat at temperatures below 45 °C and using booster heat pumps at the customers' substations to provide the appropriate temperature needed for space heating and domestic hot water production. As such, thermal networks would be able to abate heat losses and substantially increase the number of recoverable heat sources. At the same time, the supply temperature from the booster heat pumps can be tailored to the building supplied instead of being based on the most critical consumer. This work investigates the performance of booster heat pumps assuming network supply temperatures in the range between 15 °C and 45 °C. The impact of supply and return temperature on the levelized cost of heat for different end users was assessed. The parametric study shows the importance of the nominal network temperature difference in the design phase of the system in order to reach a good trade-off between initial investment and operating costs. The economic analysis shows that the system is already competitive with individual gas boilers provided that a local low-temperature heat source can be recovered with minor marginal costs.
File in questo prodotto:
File Dimensione Formato  
2018_Evaluating the cost of heat for end users in ultra low temperature district heating networks with booster heat pumps.pdf

non disponibili

Tipologia: Versione Editoriale
Licenza: Accesso ristretto
Dimensione 2.18 MB
Formato Adobe PDF
2.18 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11578/334069
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 59
  • ???jsp.display-item.citation.isi??? 47
social impact